2-7 3/C CPRESS CU NL-EPR 25% T/S 1X#6 CU GW ARMOR-X MC-HL OR MV-105 15KV 133% RED PVC JACKET 3000 FT
- Southwire #
- 89066389
Type MV-105 Three Conductor Copper, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Continuous Corrugated Welded Aluminum Armor - ARMOR-X®, Polyvinyl Chloride (PVC) Jacket. Silicone Free
Part of the family: CU Compressed 15kV NLEPR Insulation 133% IL ARMOR-X® Red PVC Jacket. MV 105 Tray Rated - Sunlight Resistant - For Direct Burial
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Southwire’s 15KV ARMOR-X® are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications
| Cond. Size | 2 AWG2 AWG |
|---|---|
| Cond. Strands | 77 |
| Diameter Over Conductor | 0.282 inch0.72 cm |
| Diameter Over Insulation | 0.755 inch1.92 cm |
| Insulation Thickness | 220 mils5.59 mm |
| Diameter Over Shield | 0.815 inch2.07 cm |
| Ground Size | 1x61x6 |
| Diameter Over Armor | 2.290 inch5.82 cm |
| Jacket Thickness | 85 mils2.16 mm |
| Approx. OD | 2.460 inch6.25 cm |
| Approx. Weight | 2674 lbs/1000'3979 kgs/km |
| Max Pull Tension | 1592 lbs722.12 kg |
| Min. Bend Radius | 17.2 inch43.69 cm |
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
- ASTM B496 Compact Round Concentric-lay-standard copper
- UL 1072 Medium-Voltage Power Cables
- UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- UL 2225 Cables and Cable-Fittings For Use In Hazardous (Classified) Locations
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661