DistributorSouthwire

Southwire

14-7 7/C CPRESS CU XHHW-2 1X#14 CU GW ARMOR-XTRA MC-HL CSA RA90-HL 600VBLACK PVC JACKET

Southwire #
58645099

Type MC-HL Control Cable 600Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Continuous Corrugated Welded Armor ARMOR-X®, Polyvinyl Chloride (PVC) Jacket with 1 Insulated Green CU Ground

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Southwire's 600 Volt Type MC-HL ARMOR-X® control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -40°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503.

Specifications

Cond. Size14 AWG14 AWG
Conductor Number77
Cond. Strands77
Insulation Thickness30 mils0.76 mm
Diameter Over Armor0.650 inch1.65 cm
Jacket Thickness50 mils1.27 mm
Approx. OD0.756 inch1.92 cm
Copper Weight89 lbs/1000'132 kgs/km
Approx. Weight248 lbs/1000'369 kgs/km
DC Resistance at 25C2.631 ohms/1000'3.92 ohms/km
AC Resistance at 75C3.170 ohms/1000'4.72 ohms/km
Min. Bend Radius5.3 inch13.46 cm
Allowable Ampacity Raceway 75C1616
Allowable Ampacity Raceway 90C2020

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • UL 2225 Cables and Cable-Fittings For Use In Hazardous (Classified) Locations
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)