DistributorSouthwire

Southwire

10-7 11/C CPRESS CU XHHW-2 1X#10 GG ARMOR-X MC-HL 600V BLACK PVC JACKET

Southwire #
55062399

Type MC-HL Control Cable 600Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Continuous Corrugated Welded Armor ARMOR-X®, Polyvinyl Chloride (PVC) Jacket with 1 Insulated Green CU Ground

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Southwire's 600 Volt Type MC-HL ARMOR-X® control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -40°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503.

Specifications

Cond. Size10 AWG10 AWG
Conductor Number1111
Cond. Strands77
Insulation Thickness30 mils0.76 mm
Diameter Over Armor1.020 inch2.59 cm
Jacket Thickness50 mils1.27 mm
Approx. OD1.126 inch2.86 cm
Copper Weight386 lbs/1000'574 kgs/km
Approx. Weight699 lbs/1000'1040 kgs/km
DC Resistance at 25C1.040 ohms/1000'1.55 ohms/km
AC Resistance at 75C1.253 ohms/1000'1.86 ohms/km
Min. Bend Radius7.9 inch20.07 cm
Allowable Ampacity Raceway 75C1717
Allowable Ampacity Raceway 90C2020

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • UL 2225 Cables and Cable-Fittings For Use In Hazardous (Classified) Locations
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)