DistributorSouthwire

Southwire

CU 600V Power Drop Cable

Southwire #
SPEC45028

600V Flexible CU THHN Power Cable TC-ER

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (4) ↓

Available sizes & constructions

Cond. SizeConductor NumberCond. StrandsDiameter Over Conductor (in)(cm)Insulation Thickness (mils)(mm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Copper Weight (lbs/1000')(kgs/km)Approx. Weight (lbs/1000')(kgs/km)
6 AWG6 AWG332732730.1900.48350.89601.520.7551.92297442461686 64894799
4 AWG4 AWG334134130.2350.60350.89802.030.9572.434476657001042 64894299
2/0 AWG2/0 AWG33133013300.4201.07601.52802.031.4513.691326197319812948 64727599
373.7 KCMIL373.7 KCMIL339319310.7101.80701.781102.792.0555.223539526744786664 64728099
6 AWG6 AWG333.07.62629285.310.4110.610.4950.740.0510.0865657575 64894799
4 AWG4 AWG333.89.651001454.050.2580.380.3100.460.0480.0785859595 64894299
2/0 AWG2/0 AWG337.318.5431941448.770.0810.120.0970.140.0430.06175175195195 64727599
373.7 KCMIL373.7 KCMIL3312.331.2429901356.240.0330.050.0350.050.0400.06323323365365 64728099

Part numbers in this family (4)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
648947996-273 CU 3/C THHN BK/RD/BU 8-168 GG PVC JKT TYPE TC-ER 600V/AWM 20886 1000V6 AWG 3C 273SBLACK/RED/BLUECUT TO LENGTH REEL
648942994-413 CU 3/C THHN BK/RD/BU 8-168 GG PVC JKT TYPE TC-ER 600V/AWM 20886 1000V4 AWG 3C 413SBLACK/RED/BLUECUT TO LENGTH REEL
647275992/0-1330 3/C CU THHN/PVC BLACK/RED/BLUE 1x2 GG TYPE TC-ER/WTTC AWM 20886 600V BLACK2/0 AWG 3C 1330SBLACK/RED/BLUECUT TO LENGTH REEL
64728099373.7-931 3/C CU THHN/PVC BLACK/RED/BLUE 1x2 GG TYPE TC-ER/WTTC AWM 20886 600V BLACK373.7 KCMIL 3C 931SBLACK/RED/BLUECUT TO LENGTH REEL

Application & features

Southwire's 600 Volt Power Drop Cables conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays (TC-ER per NEC 336.10), direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC Article 501 and 502. Southwire's 600 Volt Power Drop Cable is ideal for use in power feed drop applications.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 509 Bus Drop Cable
  • UL 758 Standard for Appliance Wiring Material Style 20886
  • UL 1063 Machine Tool Wiring (MTW)
  • UL 1277 TC-ER
  • UL 2277 Type WTTC
  • CSA C22.2 No. 75 Thermoplastic Insulated Wires and Cables
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive