DistributorSouthwire

Southwire

CU 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Southwire #
SPEC45307

Type MC Power Cable 600Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (11) ↓

Available sizes & constructions

Cond. SizeCond. StrandsDiameter Over Conductor (in)(cm)Insulation Thickness (mils)(mm)Diameter Over Armor (in)(cm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Approx. Weight (lbs/1000')(kgs/km)Max Pull Tension (lbs)(kg)Min. Bend Radius (in)(cm)
6 AWG6 AWG770.1770.45451.140.8652.20501.270.9652.45650967671304.366.817.27 57446099
2 AWG2 AWG770.2820.72451.141.1132.83501.271.2133.08127919031698770.208.521.59 58073099
1/0 AWG1/0 AWG19190.3610.92551.401.3523.43501.271.4523.691907283827031226.0610.225.91 89022999
4/0 AWG4/0 AWG19190.5121.30551.401.7854.53601.521.9054.843534525954162456.6513.333.78 56260599
250 KCMIL250 KCMIL37370.5581.42651.651.9404.93601.522.0605.234153618064002902.9914.436.58 55795989
350 KCMIL350 KCMIL37370.6611.68651.652.1795.53601.522.2995.845709849689604064.1816.140.89 55145299
500 KCMIL500 KCMIL37370.7892.00651.652.4846.31751.912.6346.69785411688128005805.9818.446.74 60541099
600 KCMIL600 KCMIL61610.8652.20802.032.7657.02751.912.9157.40930313844153606967.1720.451.82 56340799
6 AWG6 AWG0.4110.610.4950.740.0270.040.0510.08 57446099
2 AWG2 AWG0.1620.240.1950.290.0180.030.0450.07 58073099
1/0 AWG1/0 AWG0.1020.150.1220.180.0170.030.0440.07 89022999
4/0 AWG4/0 AWG0.0510.080.0620.090.0130.020.0410.06 56260599
250 KCMIL250 KCMIL0.0430.060.0530.080.0140.020.0410.06 55795989
350 KCMIL350 KCMIL0.0310.050.0390.060.0120.020.0400.06 55145299
500 KCMIL500 KCMIL0.0220.030.0290.040.0100.010.0390.06 60541099
600 KCMIL600 KCMIL0.0180.030.0250.040.0110.020.0390.06 56340799

Part numbers in this family (11)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
6 AWG (1)
574460996-7 CU 4/C 45 MILS XHHW-2 1X8 CU GW AIA PVC 600V6 AWG 4C 7SBLACK/BLACK/BLACK/BLACK/-CUT TO LENGTH REEL
2 AWG (1)
580730992-7 CU 4/C 45 MILS XHHW-2 1X6 CU GW AIA PVC 600V2 AWG 4C 7 STRBLACK/BLACK/BLACK/BLACKCUT TO LENGTH REEL
1/0 AWG (1)
890229991/0-19 CU 4/C 55 MILS XHHW-2 1X6 CU GW AIA PVC 600V1/0 AWG 4C 19SBLACK/BLACK/BLACK/BLACKCUT TO LENGTH REEL
4/0 AWG (1)
562605994/0-19 CU 4/C 55 MILS XHHW-2 1X4 CU GW AIA PVC 600V4/0 AWG 4C 19 STRBLACK/BLACK/BLACK/BLACKCUT TO LENGTH REEL
250 kcmil (2)
55795999250-37 CU 4/C 65 MILS XHHW-2 1X4 CU GW AIA PVC 600V250 KCMIL 4C 37SBLACK/BLACK/BLACK/BLACKCUT TO LENGTH REEL
55795989250-37 CU 4/C 65 MILS XHHW-2 1X4 CU GW AIA PVC 600V 3000 FT250 KCMIL 4C 37SBLACK/BLACK/BLACK/BLACK3000 FT REEL
350 kcmil (2)
55145299350-37 CU 4/C 65 MILS XHHW-2 1X3 CU GW AIA PVC 600V350 KCMIL 4C 37SBLACK/BLACK/BLACK/BLACKCUT TO LENGTH REEL
66851999350-37 CU 4/C 65 MILS XHHW-2 1X2/0 CU GW AIA PVC 600V350 KCMIL 4C 37SBLACK/BLACK/BLACK/BLACKCUT TO LENGTH REEL
500 kcmil (1)
60541099500-37 CU 4/C 65 MILS XHHW-2 1X2 CU GW AIA PVC 600V500 KCMIL 4C 37SBLACK/BLACK/BLACK/BLACKCUT TO LENGTH REEL
600 kcmil (2)
56340799600-61 CU 4/C 80 MILS XHHW-2 1X2 CU GW AIA PVC 600V600 KCMIL 4C 61SBLACK/BLACK/BLACK/BLACKCUT TO LENGTH REEL
67298999600-61 CU 4/C 80 MILS XHHW-2 1X4/0 CU GW AIA PVC 600V600 KCMIL 4C 61SBLACK/BLACK/BLACK/BLACKCUT TO LENGTH REEL

Application & features

Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE, 4-ORANGE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy