
![]()
6-7 CU 3/C 45 MILS XHHW-2 1X8 CU GW AIA PVC 600V
- Southwire #
- 60694799
Type MC Power Cable 600Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.
Part of the family: CU 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.
Specifications
| Cond. Size | 6 AWG6 AWG |
|---|---|
| Cond. Strands | 77 |
| Diameter Over Conductor | 0.177 inch0.45 cm |
| Insulation Thickness | 45 mils1.14 mm |
| Diameter Over Armor | 0.788 inch2.00 cm |
| Jacket Thickness | 50 mils1.27 mm |
| Approx. OD | 0.888 inch2.26 cm |
| Approx. Weight | 545 lbs/1000'811 kgs/km |
| Max Pull Tension | 629 lbs285.31 kg |
| Min. Bend Radius | 6.2 inch15.75 cm |
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 44 Thermoset-Insulated Wires and Cables
- UL 1569 Metal-Clad Cables
- UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
- ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)