CU 2000V XLPE Insulation Type RHH/RHW-2. 600V Type USE-2
- Southwire #
- SPEC45502
Power Cable 2000 Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) Insulation for Type RHH/RHW-2 and 600 Volt for Type USE-2
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Part numbers in this family (2) ↓Available sizes & constructions
| Cond. Size | Conductor Number | Cond. Strands | Diameter Over Conductor (in)(cm) | Insulation Thickness (mils)(mm) | Approx. OD (inches)(cm) | Copper Weight (lbs/1000')(kgs/km) | Approx. Weight (lbs/1000')(kgs/km) | ||
|---|---|---|---|---|---|---|---|---|---|
| 500 KCMIL500 KCMIL | 11 | 3737 | 0.7892.00 | 1052.67 | 0.9862.50 | 15432296 | 17482601 | 56801899 | |
| 750 KCMIL750 KCMIL | 11 | 6161 | 0.9682.46 | 1203.05 | 1.2203.10 | 23153445 | 25693823 | 64875099 | |
| 500 KCMIL500 KCMIL | 11 | 3.99.91 | 40001814.37 | 0.0220.03 | 0.0290.04 | 0.0390.06 | 380380 | 430430 | 56801899 |
| 750 KCMIL750 KCMIL | 11 | 6.115.49 | 60002721.55 | 0.0140.02 | 0.0220.03 | 0.0380.06 | 475475 | 535535 | 64875099 |
Part numbers in this family (2)
By size:
Application & features
Southwire’s 2000 Volt power cables RHH/RHW are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. Can be used in direct burial applications at 600 Volt. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.
Standards & references
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- UL 44 Thermoset-Insulated Wires and Cables
- UL 854 Service Entrance Cable
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy