DistributorSouthwire

Southwire

CU 2000V XLPE Insulation Three Grounds Cu Tape Shield Thermoplastic CPE-TP Jacket. RHH/RHW-2 Variable Frequency Drive (VFD)

Southwire #
SPEC45455

Type TC VFD Power Cable 2000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2 Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket with 3 Symmetrical Bare CU Ground 50% Minimum Tape Shield Overlap. Silicone Free

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (5) ↓

Available sizes & constructions

Cond. SizeConductor NumberCond. StrandsDiameter Over Conductor (in)(cm)Insulation Thickness (mils)(mm)Diameter Over Shield (in)(cm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Copper Weight (lbs/1000')(kgs/km)Approx. Weight (lbs/1000')(kgs/km)
12 AWG12 AWG33770.0880.22601.520.4861.23601.520.6071.54128190251374 67930999
2 AWG2 AWG33770.2820.72701.780.9462.401152.921.1742.98827123112091799 67931199
2/0 AWG2/0 AWG3319190.4051.03902.291.3113.33802.031.5313.891641244223123441 67931099
4/0 AWG4/0 AWG3319190.5121.30902.291.5063.831152.921.7424.422542378332214793 67931299
500 KCMIL500 KCMIL3337370.7892.001052.672.1495.461152.922.3796.0457068491677910088 66553799
12 AWG12 AWG337.318.5415670.761.6622.472.0022.980.0570.080.0540.0825253030 67930999
2 AWG2 AWG3314.135.811592722.120.1620.240.1950.290.0270.040.0450.07115115130130 67931199
2/0 AWG2/0 AWG3318.446.7431941448.770.0810.120.0970.140.0250.040.0430.06175175195195 67931099
4/0 AWG4/0 AWG3320.953.0950782303.340.0510.080.0620.090.0200.030.0410.06230230260260 67931299
500 KCMIL500 KCMIL3328.672.64120005443.100.0220.030.0290.040.0160.020.0390.06380380430430 66553799

Part numbers in this family (5)

By size:
Southwire #DescriptionConstructionConductor ColorPackaging
6793099912-7 3/C CU RHH-RHW-2 3x16 GW T/S CPE JKT TC 2000V VFD12 AWG 3C 7S1-ONE/2-TWO/3-THREECUT TO LENGTH REEL
679311992-7 3/C CU RHH-RHW-2 3X#10 GW T/S CPE JKT TC 2000V VFD2 AWG 3C 7 STR1-ONE/2-TWO/3-THREECUT TO LENGTH REEL
679310992/0-19 3/C CU RHH-RHW-2 3X#6 GW T/S CPE JKT TC 2000V VFD2/0 AWG 3C 19 STR1-ONE/2-TWO/3-THREECUT TO LENGTH REEL
679312994/0-19 3/C CU RHH-RHW-2 3X#4 GW T/S CPE JKT TC 2000V VFD 0 FT4/0 AWG 3C 19 STR1-ONE/2-TWO/3-THREECUT TO LENGTH REEL
66553799500-37 3/C CU RHH-RHW-2 3X#1 GW T/S CPE JKT TC 2000V VFD 0 FT500 KCMIL 3C 37S1-ONE/2-TWO/3-THREECUT TO LENGTH REEL

Application & features

Southwire’s 2000 Volt Type TC VFD power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Type (TC) per NEC 336.10.

Standards & references

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA S-138-738 Power Cables Rated 2000 Volts or Less for use Between Variable Frequency Drives and Motors
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661