4/0-19 3/C 3E AL 115 NL-EPR T/S 1X4 CU GW AIA YELLOW PVC JACKET 5KV 133%/8KV 100% UL
- Southwire #
- 59778099
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Southwire’s 5KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -40°C for cold bend and cold impact and marked with "LTGG" when CSA listed or dual UL/CSA listed. For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications
| Cond. Size | 4/0 AWG4/0 AWG |
|---|---|
| Cond. Strands | 1919 |
| Diameter Over Conductor | 0.474 inch1.20 cm |
| Diameter Over Insulation | 0.743 inch1.89 cm |
| Insulation Thickness | 115 mils2.92 mm |
| Diameter Over Shield | 0.803 inch2.04 cm |
| Ground Size | 1x41x4 |
| Diameter Over Armor | 2.106 inch5.35 cm |
| Jacket Thickness | 65 mils1.65 mm |
| Approx. OD | 2.238 inch5.68 cm |
| Approx. Weight | 2267 lbs/1000'3374 kgs/km |
| Max Pull Tension | 3808 lbs1727.28 kg |
| Min. Bend Radius | 15.6 inch39.62 cm |
Standards & references
- ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
- ASTM B836 Compact Rounded Stranded Aluminum Conductors
- UL 1072 Medium-Voltage Power Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
- ICEA S-58-679 Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
- ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
- ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
- AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661