DistributorSouthwire

Southwire

3/0-15 3E AL 320 MILS TR-XLP 25KV 133% T/S BLACK SIMpull PVC JACKET UL

Southwire #
67458699

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Quote on WhatsApp

Application & features

Southwire’s 25KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications

Cond. Size3/0 AWG3/0 AWG
Cond. Strands1515
Diameter Over Conductor0.422 inch1.07 cm
Diameter Over Insulation1.101 inch2.80 cm
Insulation Thickness320 mils8.13 mm
Diameter Over Shield1.161 inch2.95 cm
Jacket Thickness80 mils2.03 mm
Approx. OD1.341 inch3.41 cm
Approx. Weight824 lbs/1000'1226 kgs/km
Max Pull Tension1006 lbs456.31 kg
Min. Bend Radius16.0 inch40.64 cm
Conduit Size4.0 inch10.16 cm

Standards & references

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 1072 Medium-Voltage Power Cables
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA S-97-682 Standard for Shielded Utility Cable Rated for 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661