DistributorSouthwire

Southwire

AL Compact 15kV NLEPR Insulation 133% IL Black SIM-PVC Jacket. 2x5 mils Tape Shield - MV 105 - Tray Rated - Sunlight Resistant - For Direct Burial

Southwire #
SPEC46313

Type MV-105 Single Conductor Aluminum, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, 2x5 Mils Tape Shield, SIMpull® Polyvinyl Chloride (PVC) Jacket, Dual Rated UL/CSA

Priced by quote — copper moves daily (COMEX), so we quote at the current price.

Part numbers in this family (3) ↓

Available sizes & constructions

Cond. SizeCond. StrandsDiameter Over Conductor (in)(cm)Diameter Over Insulation (in)(cm)Insulation Thickness (mils)(mm)Diameter Over Shield (in)(cm)Jacket Thickness (mils)(mm)Approx. OD (inches)(cm)Approx. Weight (lbs/1000')(kgs/km)Max Pull Tension (lbs)(kg)Min. Bend Radius (in)(cm)Conduit Size (in)(cm)
250 KCMIL250 KCMIL22220.5201.321.0062.562205.591.0662.71802.031.2663.2293013841500680.3915.138.353.58.89 58900299
500 KCMIL500 KCMIL34340.7351.871.2443.162205.591.3043.31802.031.5043.821341199630001360.7818.045.724.511.43 64081499
750 KCMIL750 KCMIL58580.9082.311.4263.622205.591.4863.77802.031.7464.431821271045002041.1620.953.095.012.70 58900199
250 KCMIL250 KCMIL0.0710.110.0900.130.0340.050.0420.060.447 + j0.3020.447 + j0.3020.103 + j0.0530.103 + j0.05333333333250250270270345345385385 58900299
500 KCMIL500 KCMIL0.0350.050.0460.070.0260.040.0370.060.446 + j0.4660.446 + j0.4660.081 + j0.0390.081 + j0.03939993999370370400400535535600600 64081499
750 KCMIL750 KCMIL0.0240.040.0330.050.0220.030.0350.050.446 + j0.4660.446 + j0.4660.081 + j0.0390.081 + j0.03945664566455455490490700700780780 58900199

Part numbers in this family (3)

By size:
Southwire #DescriptionConstructionPackaging
58900299250-22 3E AL 220 MILS NL-EPR 15KV 133% 2XT/S BLACK SIMpull PVC JACKET250 KCMIL 1C 22SCUT TO LENGTH REEL
64081499500-35 3E AL 220 MILS NL-EPR 15KV 133% 2XT/S BLACK SIMpull PVC JACKET500 KCMIL 1C 34SCUT TO LENGTH REEL
58900199750-58 3E AL 220 MILS NL-EPR 15KV 133% 2xT/S BLACK SIMpull PVC JACKET750 KCMIL 1C 58SCUT TO LENGTH REEL

Application & features

Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial when installed with a grounding conductor in close proximity that conforms to NEC section 311.36 and 250.4(A)(5), and where su- perior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -25°C for cold bend and cold impact and marked with "LTDD" when CSA listed or dual UL/CSA listed. ST1 (low smoke) Rated for sizes 1/0 and larger. PVC jacket is made with SIM technology and has a coefficient of friction COF of 0.2. Cable can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure. 2x5 mils tape shield for higher short circuit withstand.

Standards & references

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 1072 Medium-Voltage Power Cables
  • UL 1685 FT4-ST1 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER (1/0 AWG and Larger)
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661