350-37 MB CPRESS AL 35KV 345 mils 100% TRXLP 90C 18x14CN HiDri Plus POLY JACKET
- Southwire #
- 58452425
Aluminum Conductor. TRXLP Insulation. Bare Copper Concentric Neutrals. Low Density Polyethylene Jacket.
Part of the family: 35KV Aluminum XLP MV LLDPE Jacket
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Predominantly used for primary underground distribution in conduit systems suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 35,000 volts or less and at conductor temperatures not to exceed 90°C for normal operation.
Specifications
| No. of Conductors | 11 |
|---|---|
| Size | 350 KCMIL350 KCMIL |
| No. of Strands | 3737 |
| Insulation Thickness | 345 mils8.76 mm |
| Nom. OD | 1783 mils45.29 mm |
| Nominal Total Weight | 1463 lbs/1000'2178 kgs/km |
Standards & references
- B231: Aluminum 1350 Conductors, Concentric-Lay-Stranded
- B609: Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
- B3: Soft Annealed Copper Wire
- ICEA S-94-649
- AEIC CS-8
- RUS U-1