18/4 PAIR STR CU PVC/PVC SPOS TC BLACK
- Southwire #
- 55841499
Type PLTC/ITC Instrumentation Cable 300 Volt Copper Conductors PVC Insulated Singles Shielded Pairs with Overall Shield SPOS. PVC Jacket Heat, Moisture, and Sunlight Resistant RoHS rated for -30°C to 105°C
Part of the family: 300V CU PVC PAIRS PVC SPOS Instrumentation
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Southwire’s Instrumentation Cables Type PLTC per UL 13 and Type ITC per UL 2250 are suitable for installations as outlined in NEC Article 336 for process control and instrumentation, control circuits for operation and interconnection of protective and signaling devices and for general use in manufacturing, industrial and commercial distribution systems. Cables are con- structed with 7-strand copper conductors insulated with PVC. The paired conductors are colored black, white, and alpha-numeric printed. Each pair has an aluminum polyester foil with 100% coverage and a tinned drain wire. The overall assembly is covered with an aluminum polyester foil with 100% coverage and a tinned drain wire. The cable is suited for use in cable trays, raceways, conduit, aerial (when supported with a messenger). The cable is rated for -30°C to 105°C and rated for Class I Div II hazardous locations, and sun resistant. The jacket is black PVC with a nylon ripcord for easy removal.
Specifications
| Cond. Size | 18 AWG18 AWG |
|---|---|
| Conductor Number | 44 |
| Diameter Over Conductor | 0.045 inch0.11 cm |
| Insulation Thickness | 15 mils0.38 mm |
| Jacket Thickness | 65 mils1.65 mm |
| Approx. OD | 0.493 inch1.25 cm |
| Approx. Weight | 133 lbs/1000'198 kgs/km |
| Min. Bend Radius | 5.9 inch14.99 cm |
| DC Resistance at 25C | 6.669 ohms/1000'9.92 ohms/km |
Standards & references
- UL 13 Power-Limited Circuit Cables
- UL 2250 Instrumentation Tray Cable
- IEEE 383 Flame Test (70,000 btu)
- IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
- EPA 40 CFR, Part 26, Subpart C heavy metals per Table 1, TCLP method
- RoHS-2 (European Directive 2011/65/EU)
- NEC Article 336 Power and Control Tray Cable