
![]()
750-61 MB CPRESS CU 15KV 220 mils 133% EPR 105C 25x10CN POLY JACKET
- Southwire #
- 60662699
Aluminum or Copper Conductor. EPR Insulation. Bare Copper Concentric Neutrals. Low Density Polyethylene Jacket.
Part of the family: 15KV Copper EPR MV LLDPE Jacket
Priced by quote — copper moves daily (COMEX), so we quote at the current price.
Application & features
Predominantly used for primary underground distribution in conduit systems suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 15,000 volts or less and at conductor temperatures not to exceed 105°C for normal operation.
Specifications
| No. of Conductors | 11 |
|---|---|
| Size | 750 KCMIL750 KCMIL |
| No. of Strands | 6161 |
| Insulation Thickness | 220 mils5.59 mm |
| Nom. OD | 1925 mils48.92 mm |
| Nominal Total Weight | 4142 lbs/1000'6164 kgs/km |
Standards & references
- B3: Soft Annealed Copper Wire
- B8: Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft
- ICEA S-94-649
- AEIC CS-8
- RUS U-1